             98AR Thermal Circuit Breaker

             Single Pole Auto- Reset


             •Technical data
             •Current rating range  3~50A
             •Input voltage rating  125/250VAC; 32VDC
             •Contact Endurance  125Vac X150% of rated current >500 cycles
                              125Vac X200% of rated current >200 cycles
              •Insulation Resistance  >100MOHM (DC 500V)
              •Dielectric Strength  > 1,500VAC/min.
              •Degree of protection  Terminal area IP00,  operating area IP40
              •Mechanical/Environmental Data
              •Operating Ambient Temperature: -10  to +60℃  ℃
              •Termination: 110’’(2.8mm)quick connects or solder terminals
              •Mounting: Various options. See Ordering Information and drawings
             •Compliance with Rohs                                                                      MADE IN TAIWAN  XXA  98 Series  KUOYUH
              The product accords with the requirement of ROHS( 2011/65/EU)
              Contacts use Exempted item of RoHS Directive 2010/571/EU 8(a)                             C   SUD  R
             •Compliance with REACH, PAHS, PH1, PH2, PH3                                                US  Rohs Ignition Protected  S  32VDC  T . V . U . .
             •Typical applications                                             LINE       LOAD          TC2/OL0/C1  125/250VAC  Suppl.Prot.  125/250VAC
               Tarnsforms, Motors, Battery chargers, Power supplies,
             •Calibration(at25 )℃
              •100% of Rated Current:      Hold , No Trip
              •150% of Rated Current:      Trip Within 1 Hour.    •98AR 3A-50A Trip Time Curves
              •200% of Rated Current:      5-30 sec Trip
              •300% of Rated Current:      1.5-5.0 sec Trip           1000%
                                                                                                     3Amp-50Amp  (sec)
             •Approval                                                800%                       OverLoad  3A~30A  31A~50A
                                                                                                  600%  0.45~1.2  0.68~2.4
                                                                                                      0.58~1.8
             •Approval & File No.       Rated current     Rated voltage  600%                     500%  0.8~3.7  0.8~3.2
                                                                                                          1.8~4.5
                                                                                                  400%
             •CUL UL E155159       3-50A    12VDC                     500%                        300%  1.8-5.5  3.2~7.7
                                                                    Load Current AS Percent of  Circuit Breaker Rating  300%
                                                                                                          7.8~40.0
                                                                                                  200%
                                                                                                      5.0-28.0
                                                                                                        Trip in 1 Hour
             •TUV SUD B15 09 58611 007  3-30A  125/250VAC; 32VDC                                  150%  Hold, No Trip
                                                                                                  100%
                                                                      400%
             •Order Guide                                             200%
                                                                      150%
                                                                      100%
               98AR       -  2 0 - AR          1      N                 0.1     1      Time in Seconds  100  1000  10000
                                                                                       10
                                                                                  Trip Curves Are Specified of 25°C/77°F
                 Series No.  Amp Rating  Bushing  Terminal  Terminal finish
                                                                   •Ambient Temperature Correction Factor
                                                                    Ambient
              03=  3A                              S= Plate with Tin  temperature  -10°C  0°C  10°C  25°C  35°C  40°C  50°C  60°C
                 4A                                N= Plate with Nickel  Multiplication  *1.30  *1.20  *1.10  1.00  *0.94  *0.85  *0.73  *0.68
                                                                    factor
              04= . . . . .
              40=  40A
                                                                   The time/current characteristic curve depends on the ambient temperature prevailing. In order to
              50=  50A
                                                                   eliminate nuisance tripping. Please multiply the circuit  breaker current ratings by the derating
                                                                   factor shown below.
              ZJ  Auto-Reset  AR  Auto-Reset
                                                                   Example : Normal Continuous Current = 10A
                                                                         Ambient Temperature = 45°C
                                                                         Multiplication Factor =  0.85
                                                                         Recommended Rating= 10A/0.85=11.8A
                                                                         Select the Nearest Rating = 12A
                                                                    •Max.Internal Resistance  •Internal connection diagram
                                                                       Amp rating  Max resistance
                                                                         3~5 A   <0.225 Ohms              Load
                1     2     3      F     L      J                        6~8 A   <0.175 Ohms
             Straight  11.8mm  90° bend  90° bend  Screwa  Screwa  #8-32  Screwa  #8-32
                                Straight  90° bend  up  90° bend  down  9~11 A   <0.125 Ohms
                                                                        12~13 A  <0.050 Ohms
                                                                        14~17 A  <0.040 Ohms
                                                                        18~24 A  <0.030 Ohms
                   11.8                 #8-32  #8-32                    25~35 A  < 0.020 Ohms
                                 #8-32                                                                    Line
                                                                        36~50 A  < 0.010 Ohms
      * The specification subject to change without notice. The drawing is for reference only.
      KUOYUH  W.L. Enterprise Co.,Ltd.
      No.17 Kejia 6th Road Douliu City YunLin Hsien 64057  Taiwan R.O.C
                                                                                                      國郁企業股份有限公司
      http//www.kuoyuh.com.tw     sales@kuoyuh.com
                                                                                                      64057 雲林縣斗六市科加六路17號
      Taiwan Tel: 886 5 551 3222  Fax: 886 5 551 3030
      China Tel: 86 769 8366 6388  Fax: 86 769 8366 6362
      Issue:A0                                                                                                  P21
      Date:2017.02.20
   17   18   19   20   21   22   23   24   25   26   27